[ TOOLS / GV-CALC-01 ]
GVoltt Battery Calculator
Size lead-acid banks for Caribbean heat and estimate what they are worth at end of life.
Result
Energy drawn from bank8.89 kWh
Required capacity463 Ah
Configuration4S × 3P
Total units12
Installed nameplate28.8 kWh
Expected life at site temp5.5 yrs
Includes IEEE 485 aging factor 1.25. Life derated by 50% per 8°C above 25°C. Engineering estimate only — confirm with manufacturer data.